ACF6010 Series

, ,

The ACF6010 Series uses the Coriolis effect as a technique for mass flow measurement of the fluid. It can also directly measure the density and temperature.
The ACF6010 can be used for liquids and gases; the infrared keypad makes it easy for you to set parameters & change the display data in hazardous environments. The Double-V tube and Double-U tube design make it possible for the meter to be used in most fluid applications.

  • Can be programmed by the infrared keypad without opening the cover
  • High turndown ratio of flow rate
  • Multiple flange types are available, such as ANSI, DIN, JIS, etc.
  • Excellent for high-pressure applications
  • Simple for installation, commission and maintenance
  • Self-diagnostic capabilities, cable faults, pipe vibration
  • High accuracy of +/-0.2% of reading (or +/-0.1% of reading)
  • With forward / reverse flow rate measurement function
  • Large-screen LCD display for easy viewing and operation on-site
ensor Type : U tube (2-40 mm) / V tube (50-150 mm)
Size : 2-150 mm (1/12″-6″)
Flow Range : 0-160 kg/hr~0-580000 kg/hr
Accuracy : +/-0.2% +/-ZS of reading (Standard)
: +/-0.1% +/-ZS of reading (Option)
Repeatability : +/-0.03% +/-ZS of reading
Density Range : 200-3000 kgf/m3 (0.2-3.0 g/cm3)
Accuracy : +/-0.002 g/cm3
Temperature Range : -50~125 °C (Standard)
: -50~350 °C (Option, Remote Only)
Ambient Temperature : -40~60 °C
Max. Pressure : 100 kgf/cm2
Material
Wetted Parts & Flange : S.S. 316L, Hastelloy C22
Sensor Housing : Stainless Steel 304
Junction Box : Aluminum Alloy (Epoxy Paint)
Process Connection : Flange
Flange Type : JIS 10K / JIS 20K / JIS 40K
: ANSI 150# / ANSI 300# / ANSI 600#
: DIN PN10 / PN16 / PN25 / PN40
Protection Class : IP67
: Explosion Proof, Ex d eb [ib] IIC T6 (Option)
Signal Cable Length : 10-150 m
Display : 4 lines LCD with illumination
Flow Rate Unit : g/s, kg/m, kg/hr, t/hr, lb/m, gal/m… (8 Digits)
Density Unit : kg/m3, g/cm3, lb/Usgal (5 Digits)
Totalizer Unit : g,kg,T,L,m3,Nm3,lb,gal,lb,ft3…(11 Digits)
Temperature : °C, °F (6 Digits)
Keypad : Infrared light sensor, can be programmed
without opening the cover
Turndown Ratio : 40:1
Damping : 0.0-1.0 Seconds
Low Flow Cutoff : 0.0-3600 t/hr and 0.0-3,600,000 m3/hr
Communication : RS485 (Modbus Protocol) (Standard)
: HART Signal (Option)
Current Output : 4-20 mA(Isolated), Max. 2 channels(Option)
Load : Max. 550 W
Output Unit : Mass / Volume / Density / Temperature
Pulse Output : Active Pulse (Open Collector)
Rating : 24 VDC, 50 mA Max.
Display Orientation : 0° or 180° (Parameter Setting)
Power Supply : 90-260 VAC, 50/60 Hz or 24 VDC +/-10%
Power Consumption : 7-13 W
Cable Entry : Sensor to Converter-3/4″ G
: Signal Output / Power Supply-M20
Installation : Compact or Remote

ต้องการใบเสนอราคา

Line add : @intech2000

Email : intech@intech2000.com

Phone : 02-440-1853

Scroll to Top